Ethylene Glycol Concentration and Freezing Point: Winter Chiller Maintenance for Laser Processing Facilities in Northern Vietnam

Created on 11.28
Seasonal cold weather in northern Vietnam may create freezing risks for laser cooling systems. For metal fabrication facilities operating laser tube cutting machines, winter maintenance requires attention to coolant concentration, freezing point and proper water circuit preparation. Selecting an appropriate antifreeze mixture helps reduce the risk of freeze-related damage to cooling pipes, pumps and internal laser passages.
Laser tube cutting machine and industrial chiller in a northern Vietnam metal fabrication workshop during winter

How Ethylene Glycol Concentration Affects Freezing Point

The freezing point of an ethylene glycol solution varies with concentration. The winter maintenance guide provides the following reference values:
Ethylene Glycol Concentration
Freezing Point
39.9%
-26°C
49.3%
-38°C
56.0%
-48°C
At approximately 56% concentration, the reference freezing point reaches -48°C. Increasing the concentration further may raise the freezing point, meaning more antifreeze does not necessarily provide better protection.
Ethylene glycol concentration versus freezing point curve chart for laser chiller antifreeze mixtures
The target freezing point should be approximately 5°C below the expected ambient temperature, subject to coolant specifications and equipment manufacturer recommendations.

Winter Maintenance Steps for Laser Chillers

  • Drain existing water:
Switch off the equipment and drain deionized or distilled water from the chiller and pipes.
  • Prepare antifreeze:
Mix antifreeze and water according to the selected ratio, adding antifreeze first.
  • Refill and purge:
Fill to the specified level and remove trapped air through circulation.
  • Inspect the system:
Check water temperature, pump operation and connections for leakage.
When the daily average temperature exceeds 5°C, drain the antifreeze-containing coolant, flush the circuit with deionized or distilled water, and restore regular cooling water.
Technician draining coolant and refilling antifreeze mixture in an industrial laser chiller during winter maintenance
Antifreeze compatibility with pipes, seals and pump materials should also be confirmed before use. Antifreeze should not replace regular cooling water for year-round operation.